Circular Chart Recorder

  • Chart Size: 255mm. Major (155mm. MINI)
  • Calibration Accuracy : Better than ± 0,15% of span.
  • Minimum Span : Input less than specified below will be provided by using high gain input amplifier.
  • Range : ± 25°C To 25°C, -5 To 20°C, -50 To +50°C, 0 To 50°C (Other Range on request)
  • RTD Break : Pointer will move fully up-scale if input circuit Protection Open circuited, This feature is standard in all instruments.
  • Input Resistance : Normal greater than 15 Kohms, higher value (1 Mohms) can be given
  • Source Resistance : 500 ohm standard. It can also be made to operate from different source resistance.
  • Ambient Temp. Range : 0°C To 55°C.
  • Humidity : 5% To/90% RH.
  • Power Supply : 240V 50HZ standard, ± 10VA.C.
  • Max. Power Consumption : 20 VA approx.
  • Chart Drive : Synchronous motor working on mains supply 230V, IPH, 50Hz.
  • Chart Speed : 1 Revo. In 7 days standard ±4 HR
  • Recording System : Continuous recording by Disposable Recording Pen.
  • Number Of Inputs : Single input standard; Duel Pen recorder can also be provided and we provide with Displays & Controls as well.
  • Size : 325 x 325 x 115mm (Major) , L= 155 x H= 170x-l 12mm(Mini)
  • Panel Cut Out : 330 x 330mm. For 255mm. Chart Size.For 155mm. Chart Size.
  • Depth Behind Panel : 115mm.