LEO-CHILL PACKAGED DA SERIES OXYGEN PLANT CHILLERS

LEO-CHILL PACKAGED DA SERIES OXYGEN PLANT CHILLERS
- LEO-CHILL range of DA Series Chillers is the latest version of packaged chillers designed and tailored to specifically meet Oxygen & Nitrogen manufacturing Industries.
- LEO-CHILL range of DA Series Chillers has been engineered to offer Many Features in a Compact, Space constraint design.
- DA Series Chillers range is built with advance Dependable Controls, which give optimum performance under variable operating conditions.
- The DA Series Refrigeration unit has 2 specially designed evaporators, which are tested at 70 kg pressure.
- Evaporator 1 is for 1st stage where air from compressor enters into the evaporator at 22°C and is reduced to 10°C, and is moisture free.
- Evaporator 2 is for 2nd stage where air from drier enters into the evaporator 2,And the temperature is reduced from 15 to 16°C to 7°C, and subsequently entersthe Molecular Sieve Column for further process.
- Complete Electrical and refrigeration protection and to ensure Precise process Fluid Temperatures a Microprocessor based Controller is standard in all DA Series range of Chillers.
- All Wiring and Refrigeration circuits are Colour Coded for quick and simple servicing.
- Well-designed, easy to operate, In built Control Panel incorporating fuses, Switchgears, Terminal connectors with full function control. Micro processor temperature Controller Gauges with protection HP/LP switch (Alco), Expansion through High quality Dual Danfoss Expansion valve, LED display for fault detection.
- The DA Series are also available for larger oxygen production systems viz, 400, 500, 600, 1200.
MODEL | DA 150 | DA 200 | DA 300 |
---|---|---|---|
Capacity in Kcal/Hr | 6651 Kcal/Hr | 9431 Kcal/Hr | 13202 Kcal/Hr |
Production capacity of Oxygen in m3 | 150 | 200 | 300 |
Cooling Medium for refrigerant | Water | Water | Water |
Media to Be Cooled | Air | Air | Air |
Specific heat Air | 0.29 | 0.29 | 0.29 |
Air Inlet at Evaporator 1 | 220C | 220C | 220C |
1st Stage Air Temp at Outlet of chiller Evaporator 1 | 80C Water | 80C Water | 80C Water |
Air Inlet at Evaporator 2 after Drier | 160C | 160C | 80C Water |
2nd Stage Air Temp at Outlet of chiller Evaporator 2 | 70C | 70C | 70C |
Air Flow rate through chiller | 900 Nm3/Hr | 1200 Nm3C/Hr | 1850 Nm3C/Hr |
Air Pressure at inlet of chiller | 50 Kg/cm2g | 50 Kg/cm2g | 50 Kg/cm2g |
Refrigerant Consumed | R407C | R407C | R407C |
Condensing Temperature | 400C | 400C | 400C |
Evaporation Temperature | 00C | 00C | 00C |
Compressor Make | Emmerson | Emmerson | Emmerson |
Type | Reciprocating | Reciprocating | Reciprocating |
Power input in Kw | 2.95 kw | 3.8 kw | 4.9kw |
Total BHP Consumed at Compressor | 4.0BHP | 5.0BHP | 6.6BHP |
Condensor Type | Water cooled | Water cooled | Water cooled |
Evaporator Type | Shell & Tube | Shell & Tube | Shell & Tube |
Qty | 2 Nos | 2 Nos | 2 Nos |
Total Electrical Power Requirement | 4 HP | 5 HP | 7 HP |