1302, Dharani Arcade, Anjurphata, Bhiwandi-421305, Dist. Thane, Maharashtra

...

Three Phase Inverter (Un-balance)

  • Un balance output :
    Suitable for any type of load

  • IGBT based inverter:
    Rugged design, can deliver 5 times peak output current, suitable for lift without A/C drive, Air conditioner & Industrial Loads

  • IGBT based SMPS battery charger :
    Wide input voltage range Low ripple dc charging current Less heating of batteries so battery life improves

  • Automatic changeover Using 3 phase contractors:
    No attendant required
  • Rating:
    8 KVA TO 100 KVA

  • AC input:
    415V + 15%, -20% Three Phase 4 Wire

  • Frequency:
    50Hz + 6%

  • DC VOLTAGE:
    120VDC TO 360VDC

  • Charging time:
    15 Hours for 90% of full capacity

  • Charger type:
    SMPS charger (IGBT Based)
  • Charging time:
    15 Hours for 90% of Full Capacity
  • Inverter:
    IGBT high frequency PWM
  • Change Over:
    Electro Mechanical (Switch Contactor) — Provided as standard
  • Static Switch:
    Optional
  • Technology:
    IGBT, High Frequency PWM

  • Output voltage:
    400V / 415V AC three phase

  • Voltage regulation:
    +2% for DC I/P Variation & O/P Load Variation

  • Frequency:
    50Hz + 1%

  • Waveform:
    Pure sine Wave

  • Harmonic Distortion:
    Less Than 3% for Linear Load

  • Inverter Efficiency:
    >90% for 360 VDC, >85% for 180 VDC

  • Power Factor:
    0.8

  • Over Load:
    105% Continuously, 500% for 2 Sec.

  • Allowed Imbalance:
    100%

  • Crest Factor:
    4:1

  • Transient Response:
    + 4% under full load change & corrected within 60 msec

  • Phase displacement:
    120º + 1º

  • Audible Noise:
    Less Than 45db at 1 meter

Output overload & short circuit, Output Under & Over voltage, DC Under & Over Voltage input under & over voltage, single phasing & phase unbalance.

  • Mains on :
    LED Indication

  • Inverter on:
    LED Indication

  • Battery Low:
    LED Indication & alarm

  • Input Under Voltage:
    Mains LED slow blinking

  • Input Over Voltage:
    Mains LED fast blinking

  • Output Over load:
    LED Indication & alarm

  • Plus LCD display for Input Voltage, Output Voltage, Output Current, Battery Voltage & Battery Charging Current.

  • Elector Mechanical – (switch Contractor):
    Provided as standard feature

  • Static Switch:
    BI – Directional (Optional )

  • Input:
    MCB Provided

  • Output:
    Switch,MCB(Optional)

  • Battery:
    Fuse Link, MCB (Optional)
  • UNBALANCE SINE WAVE THREE PHASE INVERTER FOR 3 PHASE MOTORS WITHOUT V/F DRIVE

  • Motor 3.5 Kw* (5 H.P.)
    • 8Kva 144V : 1
    • 12Kva 80V : 1 + Lightening Load
    • 16Kva 240V : 2
    • 24Kva 300V : 2 + Lightening Load
    • 32Kva 360V : 4
    • 48Kva 360 : 6
    • 65Kva 360 : 8
    • 80Kva 360 : 10
    • 100Kva 360 : 12
  • Motor 5.5 Kw*(7.5 H.P.)
    • 12Kva 80V : 1
    • 16Kva 240V : 1 + Lightening Load
    • 24Kva 300V : 2
    • 32Kva 360V : 2 + Lightening Load
    • 48Kva 360 : 3
    • 65Kva 360 : 5
    • 80Kva 360 : 6
    • 100Kva 360 : 8