Online UPS (ONE PHASE IN, ONE PHASE OUT)

Type 1 Phase Input – 1 Phase Output
Technology DSP based Double Conversion Online UPS system with true galvanic isolation
Ratings 2 KVA 3 KVA 5 KVA 6 KVA 8 KVA 10 KVA
Model No SW112OU SW113OU SW115OU SW116OU SW118OU SE1110OU
Capacity 2 KVA 3 KVA 5 KVA 6 KVA 8 KVA 10 KVA
INPUT
No. of Phases 1Phase-3Wire P,N,E
Voltage Range 170 V – 280 Volts AC
Input Frequency Range 47 to 53Hz.
OUTPUT
Power 1400 W 2100 W 3500 W 4200 W 5600 W 7000 W
Load PF Range 0.8 lagging
Phase 1 Phase -2 Wire (P,N)
Output Waveform Pure Sine Wave
Voltage 230 V +/-1%
Frequency 50Hz +/-0.1%
Load Crest Factor > 3:1
Output Voltage THD <=3% on Linear Load
Loading Capacity 110% for 2 Minutes
Capacity 125% continues Maintenance By-Pass Available
BY-PASS
Maintenance By-Pass Available
BATTERIES
No. of 12V Batteries 6 8 Dec-15 Dec-15 15/16 15/16
Voltage 72 VDC 96 VDC 144 VDC 144 VDC 180 VDC 180 VDC
180 VDC 180 VDC 192 VDC 192 VDC
Battery Charging current 3 Amp to 8 Amp 4 Amp to 10 Amp
Battery Recommendation From 18 Ah to 200 Ah
BATTERIES
No. of 12V Batteries 6 8 Dec-15 Dec-15 15/16 15/16
Voltage 72 VDC 96 VDC 144 VDC 144 VDC 180 VDC 180 VDC
180 VDC 180 VDC 192 VDC 192 VDC
Battery Charging current 3 Amp to 8 Amp 4 Amp to 10 Amp
Battery Recommendation From 18 Ah to 200 Ah
GENERAL
Indication LCD panel
Alarm Mains Failure, Battery Low, Over Load Short Circuit
Protection Short Circuit , Over Voltage & Under Voltage Protection.
Cooling Forced Air Cooling
UPS Efficiency > 85%
Operating Temperature 0-45DegC
Operating Humidity 95% Condensing
Acoustic Noise <45 Db at 1 meter
Protection Class Ip20
UPS Weight 32Kg 40Kg 57.5Kg 71.5Kg 93Kg 108Kg
(Without Batteries) (Without Batteries) (Without Batteries) (Without Batteries) (Without Batteries) (Without Batteries)
Dimension   W 210  420 210  420 260  520 260 300  660 300  660
`                     H 500 500 610 520 660 660
(in MM)       D 610