Salient Features :
• Totally Custom built design.
• High speed hot response for VAR compensation -
selectable up to 60mS.
• Harmonic Immunity through appropriate detuned
harmonic blocking reactors.
• Thyristorised Capacitor switching giving total solid state and reliable operation.
• Various protection to thyristors via
1. Spike Current.
2.Voltage transient.
3.Over current & Over temperature.
4.Supply system connection faults.
5.Self health monitoring.
• Usage of capacitors type like MPP, MD, APP, Gas filled - based on site requirement. Along with on - line health monitoring in term of uF value.
• Data Logging facility with RS - 485 PC interface.
• Alarm and Event/fault logging with date and time stamp for fault diagnosis.
• Optional GSM - SMS mode of communication for remote monitoring and control.
• Usage with specialised schemes like HT correction by LT compensation, Multiple set point PF for Mains Generator operations.
• Panels protection class based on site conditions - IP - 21 to IP - 56
Specifications :
Voltage:
415Vac - 3 - phase 50Hz.(Other Voltages & 60Hz Optional)
Current:
Max 120% of rated value.
Temperature:
Working: 0 C to 50 C ambiant
Storage: 10 C to 75 C ambiant.
Measurement Accuracy:
Class 1.0 for kW and Class 2.0 for kVAr as per
IEC - 62053 part 22,23.
Watt Loss:
1% kW of the rated kVAR value..
Response Time:
Overall hot response time for kVAr correction
within -+3% of required kVAR value - Adjustable upto 60 mS